TATTLETALE Annunciators and Magnetic Switches
TATTLETALE ANNUNCIATORS AND MAGNETIC SWITCHES

Tattletale annunciators and magnetic switches are the nerve centers that translate Swichgage contact operations into decisions and operate the alarm or shutdown device.

These switches are the electrical load carrying devices for the alarm or shutdown device. 

Tattletale annunciators indicate which monitored function failed leading to the alarm or shutdown magnetic switches do not. 

Magnetic switches operate basically as a latching relay.


Specifications :

Coil Voltage:

12 volt

518PH
518APH
518E
520APH
521PH
760A(‡)
761APH
R129A
24 volt

518PH
518APH
520APH
521PH
760A(‡)
761APH
R129A
12/24 volt*

117
117PH
MS2110
MS2111
822PH
ETS30S
120 VAC

MS2100
Magneto ignition

MS2120
M4264-1
CD ignition

MS2100
M4264-1
*Multi-voltage AC or DC systems.  See circuit desriptions below.
‡ Does not latch after shutdown signal clears, automatically resets.

 

Coil Resistances (OHMS):

Product - Coil Resistance in OHMS, or coil and resistor
117 - 18
117PH - 18
MS2100 - 288
MS2110 - 18
MS2111 - 72
MS2120 - 0.5
518PH - 339/678 for 12/24
518APH - 339/678 for 12/24
518E - 339/678 for 12/24
520APH - 339/618 for 12/24
521PH - 339/678 for 12/24
760A - 90/190 for 12/24
761APH - 18
822PH - 30
R129A - 90/190 for 12/24

Contacts (see Note 2 below):

NCH

117
117PH
MS2100 (A)
MS2110 (A)
MS2111 (A)
518PH
518APH
518E
520APH
760A
761APH
822PH
NOH

MS2100 (A)
MS2110 (A)
MS2111 (A)
518APH
518E
520APH
760A
761APH
822PH
ETS30S
NCG

MS2120 (B)
M4264-1 (B)
R129A (B)
NOG

MS2120 (B)
521PH
M4264-1 (B)
R129A (B)
(A): Dry contacts normally wired in hot circuit.
(B): Dry contacts normally wired in ground circuit.

 

Latch Type:

Energize to trip

117
117PH
MS2100
MS2110
MS2111
MS2120
760A
761APH
822PH
M4264-1
R129A
ETS30S
Energize to latch

518PH
518APH
518E
520APH
521PH
 
Reset Type:

Manual indicating

117PH
MS2100
MS2110
MS2111
MS2120
518PH
518APH
518E
520APH
521PH
761APH
822PH
M4264-1
Manual non-indicating

117
Electric non-indicating

760A
R129A
ETS30S
 

Time Delay

Before shutdown

520APH
760A
761APH
Start only

760A
761APH
After shutdown

ETS30S
 

NOTES:
The information above indicates features/configurations available for each model.

1. Coil Voltage - Coils are specific voltage rated or multiple voltage rated.
2. Contacts - This is the control circuit output. In the lathed position the NCH contact has a "hot" output. In the latched position, the NCG has a "grounded" output; in the tripped position, the NOG has a "grounded" output.
3. Latch Type - Refers to whether the magnetic coil is momentraily energized to trip or requires continuous power in the operating mode and de-energizes to trip.
4. Reset Type - Refers to manual or electric reset; manual indicating type is a TATTLETALE.
5. Time Delay - Indicates operation of the time delay.





Product Original Page